ULTIMA MOS 5 HART
8
Code Class Description
0 Success No Command-Specific Errors
1 - 15 Undefined
16 Error Access Restricted
17 - 127 Undefined
10.5 Command #141: Set Relay (Alarm) Configuration
This command configures the relay settings.
Request Data Bytes
Byte Format Description
0 Unsigned-8 Alarm Hi Relay La/nL: 0 – nL, 1 – LA
1 Unsigned-8 Alarm Hi Relay En/dE: 0 – dE, 1 – En
2 Unsigned-8 Alarm Lo Relay La/nL: 0 – nL, 1 – LA
3 Unsigned-8 Alarm Lo Relay En/dE: 0 – dE, 1 – En
Response Data Bytes
Byte Format Description
0 Unsigned-8 Alarm Hi Relay La/nL: 0 – nL, 1 – LA
1 Unsigned-8 Alarm Hi Relay En/dE: 0 – dE, 1 – En
2 Unsigned-8 Alarm Lo Relay La/nL: 0 – nL, 1 – LA
3 Unsigned-8 Alarm Lo Relay En/dE: 0 – dE, 1 – En
Command-Specific Response Codes
Code Class Description
0 Success No Command-Specific Errors
1 - 2 Undefined
3 Error Passed Parameter too large
4 Undefined
5 Error Too Few Data Bytes Received
16 Error Access Restricted
17 – 127 Undefined